EMPLOYMENT | CONTACT US | SITE MAP | LINKS | PRIVACY/LEGAL
- Project Site Map
- Case Studies
- Energy Services
- Energy Improvement
Project
- Hospital Energy
Audit
- RMCS Diagnostic
Services
- Commissioning
- Control System
Master Plan and
Commissioning
- Georgia State
Student Recreation
Center
- Retro-comm.
Poudre High School
- Retro-comm.
JNTF at Schriever
- Georgia Southern
Commissioning
- Facility Design
- Underground Chilled
Water, Sanitary
Sewer and Storm
Sewer
- Stadium Sports
Lighting
- Building Renovation
- HVAC Repair
and DDC Upgrade
- Indoor Air Quality
Services
- LonWorks Based
DDC System
- Bunger Henry
Infrastructure
- Miramar UMCS
- CDC Boiler Plant
Upgrade
- Broward Regional
Hospital Lighting
- Client List
- Discipline Expertise
About EMC Services Markets Served Experience News
Retro-Commissioning
Schriever Air Force Base, Colorado Springs, CO
Retro-Commissioning – JNTF Building (2000)


Retro-commissioning is the process of testing, troubleshooting, and adjusting systems in an existing building to achieve the original design performance.

Identify the Problem
A long history of comfort complaints and maintenance problems in a facility, combined with high energy bills.  EMC provided retro-commissioning services for the building systems at the JNTF building at Schriever AFB.   The JNTF building is a three-story building that contains high-level security operations such as administrative, computer lab and laboratory in support of U.S. Air Force Space Command.   The building is served by over 49 AHUs and 350 VAV/VAVI terminal units.  

Troubleshoot  the Problem
Retro-commissioning services were required primarily to correct comfort and maintenance problems in the buildings, including:
  • Evaluated heating and cooling load studies.
  • Created functional tests to determine if the terminal units were properly sized and operating according to original design intent.  The results of the test are shown in the table below.
  • Identified numerous failed mechanical components, such as DDC controllers, temperature sensors, damper actuators, fan speed controllers, dampers, and pressure sensors.
  • Provided 40 hours of air and water balance training, and 40 hours of DDC system controls training to technician and engineering staff so the on-site staff could continue to maintain systems in the future.
Troubleshoot the Problem
Problem Energy Wasted
Simultaneous heating and cooling
of air through AHUs.
Energy was being used to first preheat outside air to 70°F, then cooled down to 50°F.

AHUs operate 24 hours/day. Most areas unoccupied at night. Only ER, ICU, ORs required air flow during unoccupied periods.

Fan, coil energy was being used unnecessarily to provide comfortable space conditions during unoccupied periods.

Multizone temperatures reset according to fixed outside air temperature.
Air was being excessively heated and cooled. Multizone AHUs were not being controlled to meet needs of the worst-case zone.



Correct the Problem
Solution System Response Customer Response
Modification to the existing fan powered VAVI units and controls
VAVI units regained control of the conditioned space temperatures.
Comfort was restored to occupants.

Customer complaints regarding stagnant air and drafts were eliminated.

Maintenance calls and costs were down.
Hot spots throughout the building were reduced.
Reduced comfort-related maintenance calls.
Hot spots throughout the building were reduced. Improved employee productivity.
Re-balancing of airside system Airflow to the conditioned air space was reduced by 60%. Energy savings obtained by reducing fan energy use.
Redundant AHUs were shut off. Energy savings obtained by reducing fan energy use.
Outside air/exhaust air systems were balanced to maintain building pressurization. Achieved improved IAQ and HVAC control.
Re-balancing of waterside components Chilled water requirements for central plant pumps were reduced by over 40%. Energy savings obtained by reducing pump energy use.
Less chiller energy required to serve chilled water system Energy savings obtained by reducing chiller energy use.
Less heating energy was required for the MAUs. Energy savings obtained due to reducing heating.


Energy Savings
As a result of retro-commissioning, comfort and maintenance problems were resolved and significant energy savings were realized.  Energy savings is summarized by the following areas:

Energy Savings
Savings Opportunity Energy Savings In: Potential Energy Savings
Re-balancing airside systems (VAVI) AHU Supply Fan $150,000 to $190,000
Re-balancing waterside systems (VAVI Coils) Central Plant Cooling $25,000 to $40,000
Re-balancing waterside systems (Pumps) Chilled Water Pumps $5,000 to $8,000
Modify control of preheat coils in MAUs Central Plant Heating $2,000 to $4,000
Modify control sequence of evap. cooling - MAUs Evap. Cooling Pump $500 to $1,000
Total Annual Estimated Savings $180,000 to $240,000
Simple Payback < 2 years