EMPLOYMENT | CONTACT US | SITE MAP | LINKS | PRIVACY/LEGAL
- Project Site Map
- Case Studies
- Energy Services
- Energy Improvement
Project
- Hospital Energy
Audit
- RMCS Diagnostic
Services
- Commissioning
- Control System
Master Plan and
Commissioning
- Georgia State
Student Recreation
Center
- Retro-comm.
Poudre High School
- Retro-comm.
JNTF at Schriever
- Georgia Southern
Commissioning
- Facility Design
- Underground Chilled
Water, Sanitary
Sewer and Storm
Sewer
- Stadium Sports
Lighting
- Building Renovation
- HVAC Repair
and DDC Upgrade
- Indoor Air Quality
Services
- LonWorks Based
DDC System
- Bunger Henry
Infrastructure
- Miramar UMCS
- CDC Boiler Plant
Upgrade
- Broward Regional
Hospital Lighting
- Client List
- Discipline Expertise
About EMC Services Markets Served Experience News
Retro-Commissioning
HVAC Assessment/Retro-Commissioning
Poudre High School; Fort Collins, Colorado


Building Profile
Poudre High School is primarily a single-story brick building with a floor area of 275,000 SF.  The original building was constructed in 1963, and a major building renovation was completed in 1995.  The remodel project included installation of 18 rooftop air handling units (RTUs), which provide heating and cooling to approximately 60% of the building.  The existing RTUs are constant volume, single-zone systems with DX cooling and hot water heating capability.  Reheat coils serve each individual room.

Retro-Commissioning Tasks
Retro-commissioning at Poudre High School included the following tasks:
  • Perform cooling and heating load calculation
  • Evaluate RTU capacity, operation and schedules
  • Test airflow quantities to individual rooms
  • Test temperature calibration of space temp. sensors
  • Review RTU control sequences
  • Review control component location and function
  • Recommend modifications to mechanical systems
  • Implement new control sequence
  • Evaluate trend data of space and RTU temperatures
Deficiencies Identified
During retro-commissioning, the following mechanical problems were identified and corrected:
  • Access panel was found open in mechanical chase.  It is estimated that nearly 2,000 cfm was not serving ground floor classrooms.
  • Branch ducts and diffusers in ground floor classrooms were undersized. Ducts were upgraded.
  • Space temperature sensors were 2 to 6°F out of calibration.  Sensors were replaced.
  • Mixed air sensor was mounted downstream of DX cooling coil.
  • Control sequence was configured for an outside air reset strategy that promoted comfort, not energy savings.


Solutions/Savings Potential
A new controls sequence was implemented that employs discharge air temperature reset based on space load.  Savings will result from:

  • Improved economizer operation
  • Reduced DX compressor operation
  • Reduced simultaneous heating and cooling through reheat coils
  • Improved space temperature calibration
  • HVAC energy savings estimated at $35,000 per year