EMPLOYMENT | CONTACT US | SITE MAP | LINKS | PRIVACY/LEGAL
- Project Site Map
- Case Studies
- Energy Services
- Energy Improvement
Project
- Hospital Energy
Audit
- RMCS Diagnostic
Services
- Commissioning
- Control System
Master Plan and
Commissioning
- Georgia State
Student Recreation
Center
- Retro-comm.
Poudre High School
- Retro-comm.
JNTF at Schriever
- Georgia Southern
Commissioning
- Facility Design
- Underground Chilled
Water, Sanitary
Sewer and Storm
Sewer
- Stadium Sports
Lighting
- Building Renovation
- HVAC Repair
and DDC Upgrade
- Indoor Air Quality
Services
- LonWorks Based
DDC System
- Bunger Henry
Infrastructure
- Miramar UMCS
- CDC Boiler Plant
Upgrade
- Broward Regional
Hospital Lighting
- Client List
- Discipline Expertise
About EMC Services Markets Served Experience News
Hospital Energy Audit
US Air Force Academy
Base Hospital Energy AuditC


Purpose:
To identify and recommend energy conservation opportunities (ECOs) with a positive economic payback.

Description of Facility:
Full Service Hospital, 150,000 SF
  • Surgical
  • Outpatient Clinics
  • Labor & Delivery
  • Laboratory
  • Emergency Clinic
  • Pharmacy
  • ICU/Patient Wards
  • Food Service
  • Nuclear Medicine
Facility Energy Usage:
Energy Usage
(MBtu)

Combined ECO Savings
Energy Cost: $215,000
Energy Reduction 50-60%
Simple Payback 2.6 years







Baseline EUI: 295 kBtu/SF/year
DoD Average: 209 kbtu/SF/year











Energy Conservation Opportunties:
The energy audit identified and recommended 16 ECOs with positive economic payback. The following is a summary of those ECOs:
  • Automated Controls
    Preheat Coil
    Scheduled Start/Stop
    Hot/Cold Deck Reset
    Room Temperature Setback

  • Central Plant
    Water Side Economizer
    Variable Frequency Drives
    Premium Efficiency Motors
    Chilled Water Temperature Reset

  • HVAC Systems
    Reduce Outside Air
    Recirculate Air
    Reduce Air Supply
    Constant Volume AHUs to VAV

  • Lighting Systems
    T-8 Lamps, Electronic Ballasts
    Compact Fluorescent Lamps
    Occupancy Sensors
    Daylighting Sensors
The following tables present a profile of the ECO evaluations:

Automated Controls
ECO Problem Energy Wasted
Preheat Coil Control
Simultaneous heating and cooling of air through AHUs.
Energy was being used to first preheat outside air to 70°F, then cooled down to 50°F.

Scheduled Start/Stop

AHUs operate 24 hours/day. Most areas unoccupied at night. Only ER, ICU, ORs required air flow during unoccupied periods.

Fan, coil energy was being used unnecessarily to provide comfortable space conditions during unoccupied periods.

Hot Deck/Cold Deck Reset
Multizone temperatures reset according to fixed outside air temperature.
Air was being excessively heated and cooled. Multizone AHUs were not being controlled to meet needs of the worst-case zone.

Central Plants
ECO Problem Energy Wasted
Waterside Economizer
Existing flat-plate heat exchanger was not being utilized. Chiller was operating throughout year.
Chiller was providing chilled water at 0.6 kW/ton. Cooling tower was capable of meeting winter loads at 0.2 kW/ton.
Variable Frequency Drives
Chilled water pumps were operating at constant speed. Three-way control valves were used.
Chilled water was bypassing coils at part-load. Pump motors were operating at full electrical load during part thermal load periods.
Premium Efficiency Motors
Standard efficiency motors were being utilized on some fans and pumps.
Standard efficiency motors are typically 3-8% less efficient than premium efficiency motors.

HVAC Systems
ECO Problem Energy Wasted

Reduce Outside Air:
AHU SF-4

AHU SF-4, 100% outside air unit, was being operated at constant volume rate 24 hours per day.
Medical Standards allow OR AHUs to operate at reduce air volumes during unoccupied periods.

Reduce Outside Air:
AHU SF-6

AHU SF-6, 100% outside air unit, was being operated at constant volume rate 24 hours per day. Approximately 70% of areas served are unoccupied at night and on weekends.
Air was being delivered to zones on four floors at all times. Only one floor required conditioned air 24 hours/day. Other three floors were unoccupied at nights and on weekends.

Recirculate Air to
AHU SF-6

AHU SF-6, 100% outside air unit, was being operated at constant volume rate 24 hours per day. Exhaust fan EF-3 exhausts air from space into mechanical room.
AHU SF-6 serves offices, ICU, and patient wards. These areas do not require 100% outside air. Less energy is needed to properly condition return air than is required for outside air.